Skip to content

Electrical Safety Report

1. Purpose & Scope

TBS-001 is a steel (electrically conductive) shipping container housing a direct-current electrical system alongside water and wet photo-chemistry. That combination triggers a reasonable concern about electrical safety. This report assesses the hazards specifically created by that environment, documents the controls already in the design, and specifies the protective measures added to close the residual gaps.

It covers the 12 V DC power system (solar → MPPT → LiFePO4 → distribution → loads), its interaction with the conductive enclosure and the wet zones, and the two AC interfaces — the external shore-power charger and the dedicated Circuit-E cooler inverter (12 V→120 V; isolation/GFCI design in electrical §7.6). It does not re-derive the power budget or component selection — see the Electrical Report.


2. The Key Insight — This Is a Fire-Risk Problem, Not a Shock Problem

The intuition "electricity + liquids + a conductive metal box = electrocution" is the right instinct to check, but it largely does not apply here, because of one deliberate architectural choice:

Everything inside the container runs at 12 V DC. There is no grid-AC distribution inside the container (Electrical Report §2).

12 V DC is Extra-Low Voltage (ELV) — below every shock-safety threshold in the recognized standards, including wet and immersed conditions:

Condition Conventional safe touch-voltage limit (DC) TBS-001
Dry ≤ 120 V DC (IEC 61140 / 60364-4-41 SELV) 12 V ✓
Wet / damp location ≤ 60 V DC 12 V ✓
Immersed / submerged body ≤ 30 V DC (and lower in some codes) 12 V ✓

A worst-case wet contact (12 V across a ~300 Ω immersed-body resistance) is ~40 mA DC — perceptible, but an order of magnitude below the ~300 mA+ ventricular-fibrillation threshold for DC, which is itself far higher than for AC (IEC/TS 60479-1 body-current effects). You cannot get a dangerous shock from the 12 V system, even standing in chemistry.

The one exception — Circuit E. A single 12 V→120 V pure-sine inverter powers the outdoor evaporative cooler; its 120 V AC output is a real shock hazard. It is the only AC originating inside the box, kept off the 12 V distribution and contained by a GFCI + single-point-bonding design (electrical §7.6) — assessed as Hazard #6 below. Everything else in the container is 12 V ELV.

So for the 12 V system the hazard model shifts from electrocution → fire / arc / corrosion / thermal. The LiFePO4 pack can deliver hundreds-to-thousands of amps into a fault, and DC arcs do not self-extinguish (no current zero-crossing), so the real exposures are sustained short-circuit arcing, conductor/joint heating, and corrosion-driven faults — all of which are controlled by fusing, isolation, sealing, and bonding, not by insulation against shock.

The closest applicable standard is ABYC E-11 — AC & DC Electrical Systems on Boats: a low-voltage DC system in a conductive enclosure exposed to water and spray is functionally the marine case, and E-11 (not the AC-oriented NEC) is the right yardstick for fuse placement, conductor protection, and bonding.


3. Controls Already in the Design

These were specified independently of this review and form a sound baseline.

Control What it does Source
12 V DC distribution; AC isolated to Circuit E Eliminates the lethal-voltage path for every interior load except the one isolated, GFCI-protected cooler inverter (Hazard #6) Elec §2, §7.6
LiFePO4 chemistry No thermal runaway (unlike NMC / lead-acid); rated −20 to +60 °C for the hot container; internal per-cell BMS (over-current / over-temp / over-discharge) Elec §5.2
Layered fusing 200 A main fuse at the battery + per-circuit fuses (Blue Sea block) + 30 A per-string solar fuses Elec §7
Negative-ground bonding Steel shell bonded to battery-negative (4 AWG) + 8-ft earth stake — a positive-to-shell fault becomes a short the fuse clears Elec §7.3
IP-rated enclosures / penetrations IP65 distribution enclosure; IP67 Deutsch DT exterior connectors; IP67 MC4 solar Elec §5.4, §7.3
Protected, elevated routing Wiring in corrugated conduit + ceiling trunking, kept high and clear of the wet floor Elec §7.3

4. Hazard & Risk Assessment

Ranked by residual risk as first assessed — the Sev × Like ratings are the pre-control values for the 12 V-DC-in-a-wet-conductive-box environment; the final column tracks how each gap is now closed by the §5 controls.

# Hazard Mechanism Sev. Like. Existing control Residual gap → closed by
1 Sustained DC short / arc → fire LiFePO4 delivers huge fault current; DC arc won't self-extinguish. Chafed conductor on the steel shell, dropped tool on the busbar, or liquid bridging a terminal High Med 200 A + per-circuit fuses, BMS Main fuse far from battery; no manual disconnect; chafe not specified; PV/charge side not load-break isolatableall closed (§5 #1): terminal-mount fuse, manual disconnect + two E-stops (in/out), PV disconnect, charge-line fuse, per-pack MRBF, chafe protection
2 Corroded wet-zone connections Developer/fixer vapor + condensation attacks unsealed terminals → high-resistance joints (heating) or intermittent faults. The 5 Shurflo pumps live in the wet IBC corridor / tray end Med High IP65 enclosure (clean side only) Anderson Powerpole — not sealed; wire not tinned → closed (§5 #2): sealed IP-rated connectors + tinned wire + dielectric grease
3 Battery busbar arc-flash 200 A+ available; a dropped wrench arcs, throws molten metal, burns High Low Fusing limits duration No terminal covers; no insulated-tool note → closed (§5 #3): terminal covers + insulated-tool rule
4 Battery thermal / venting Cells can vent under BMS failure / overcharge / abuse; container reaches 60 °C, and the BMS blocks charging above ~45 °C (mid-day charge lock-out) High Low LiFePO4 (very stable), 60 °C rating, BMS Charge lock-out > 45 °C → closed (§5 #4): thermal siting — low/shaded/cooled-air (§5.2); confirm < 45 °C at commissioning
5 Shore-power AC Grid AC feeds the exterior charger only — but the site supply and any extension cord are a genuine electrocution hazard High Low AC kept exterior (IP65 charger); never distributed inside Depends on site RCD/GFCI + the operational rule → managed (§5 #5 / §6): exterior-only AC, site-RCD rule, commissioning check
6 Circuit-E cooler inverter (120 V AC) The only interior-derived AC: a 12 V→120 V inverter feeds an outdoor, water-wetted cooler beside the grounded steel box — a line-to-metal shock path High Low Separately-derived source, single-point neutral-ground bond; GFCI on the cooler outlet; shell/chassis/cooler equipotential bond; DC-side fuse + dedicated disconnect; transformer galvanic isolation (electrical §7.6) managed (§6 / §7.6): cooler unplugged + inverter DC-disconnect for transport; periodic GFCI trip test

5. Improvements — Specified & Cascaded

Each §4 residual gap is closed by a measure now part of the design — specified in full in electrical §7.5 (Circuit Protection & Electrical Safety) and §7.6 (Circuit-E AC Isolation), and priced in electrical §8 / Master Shopping List §6. This report maps each gap to its control; it does not re-specify the hardware.

Gap (Hazard #) Control Specified in
#1 — DC short / arc Two E-stops (interior + exterior) → magnetic-latch battery contactor; manual main disconnect; terminal-mount main fuse at the battery post; PV array disconnect (isolates the charge side the E-stops don't reach); MPPT charge-line fuse; per-parallel-pack MRBF fuse; chafe protection; equipotential bonding elec §7.5, §5.1–5.2
#2 — wet-zone corrosion Sealed IP-rated wet-zone connectors + tinned marine wire + dielectric grease; wet wiring elevated above the spill line with drip loops elec §7.5
#3 — busbar arc-flash Battery terminal covers + insulated-tool rule (the main disconnect also de-energizes the bus) elec §7.5
#4 — battery thermal Battery sited low + shaded + in the cooled-air path so it stays in the ≤45 °C charge window (the BMS blocks charging above ~45 °C); commissioning temperature check elec §5.2
#5 — shore AC Shore AC terminates at the exterior charger only; site RCD/GFCI rule (§6) §6
#6 — Circuit-E AC Single-point neutral-ground bond + mandatory GFCI + equipotential bond + DC fuse/disconnect + transformer galvanic isolation elec §7.6

The #1–#3 / #5 measures were the cheap, high-value first tranche; all are now specified and cascaded into the electrical BOM.


6. The Operational Rule That Matters Most

Keep the 12 V ELV boundary intact: no grid AC distributed inside the container, ever. The one designed-in AC branch — the Circuit-E cooler inverter — is deliberately isolated and GFCI-protected (§7.6); apart from it, everything inside is 12 V ELV and this is a fire-risk-management problem (fusing, isolation, sealing, bonding), not a life-safety electrocution one.

  • The shore-power AC input terminates at the exterior Victron charger only — never run an AC extension cord or generator output into the wet interior.
  • Confirm the deployment site's AC supply is on an RCD/GFCI-protected circuit before connecting the shore charger.
  • Plug the cooler into the Circuit-E GFCI outlet only during sessions; for transport, unplug it and open the inverter DC-disconnect (§7.6). Trip-test that GFCI periodically.

7. Commissioning & Periodic Checks

When Check
At commissioning Main fuse ≤180 mm from battery +; disconnect operates; shell-to-battery-negative bond < 0.1 Ω; all metalwork bonded; terminal covers fitted
At commissioning Both E-stops (interior + exterior) each trip the contactor; PV array disconnect operates; MPPT charge-line fuse present (60 A); each parallel pack has its own MRBF fuse
At commissioning Battery bay < 45 °C under peak-sun load (thermal siting, §5.2); insulation check: positive-bus-to-shell resistance high with loads off
At commissioning Circuit E: neutral-ground bonded at the inverter only; cooler-outlet GFCI trips on test; inverter chassis/cooler/shell bonded; DC disconnect operates
Before each session Wet-zone connectors seated and dry; no liquid pooling at any connection
Before each cooling session Trip-test the Circuit-E cooler-outlet GFCI; cord and outlet undamaged
Monthly Terminals for corrosion/discoloration (heat); re-grease as needed; fuse and disconnect tight
Before shore connect Site supply is RCD/GFCI-protected

8. Source References

  1. ABYC E-11 — AC & DC Electrical Systems on Boats — fuse placement (≤7"/180 mm from the source), DC conductor protection, and bonding for low-voltage DC in conductive, wet enclosures.
  2. IEC 61140 — Protection against electric shock — extra-low-voltage (ELV/SELV) limits.
  3. IEC 60364-4-41 — Low-voltage installations: protection against electric shock — SELV/PELV touch-voltage limits, including reduced limits for wet conditions.
  4. IEC/TS 60479-1 — Effects of current on human beings and livestock — body-current thresholds (DC vs AC, fibrillation).
  5. NFPA 70 (NEC) Article 690 — Solar Photovoltaic Systems — PV-side fusing and disconnect practice.
  6. Blue Sea Systems — Circuit Protection / MRBF terminal fuses & m-Series switches — terminal-mount fusing and battery disconnects.
  7. Electrical Report — power architecture, battery, wiring, and the full parts list this report draws on.
  8. Plumbing Report · Water System Report — the wet-zone pumps and where electrics meet liquids.